DERUI 10 m³ thermal chamber
10m³ Walk-In Temperature Chamber
10m³ Walk-In Temperature Chamber supports heating, cooling and dwell for large or rack-mounted assemblies. Build the quotation around the specimen, programme and required measurements.
DERUI 10 m³ thermal chamber
10m³ Walk-In Temperature Chamber for Programmed Heating, Cooling and Dwell Tests
Test large components, assemblies and rack-mounted specimens through controlled temperature profiles in a walk-in workspace. The DERUI 10m³ chamber combines programmable temperature and humidity operation with a water-cooled environmental system and controller-based test records.
Specify the required heating and cooling sequence around the real load. The selected temperature limits, transition interval, specimen mass and operating heat output determine whether a configuration can reproduce your test—not the nominal volume alone.
01 · Application
DERUI 10 m³ thermal chamber
Fit the Assembly—and Reproduce Its Temperature Profile
The 10m³ format is intended for industrial components, semi-finished goods and completed products that need a larger loading space than a cabinet provides. Review the assembly, supporting fixture and cable routes together before selecting the working dimensions.
For electronics and electromechanical assemblies, define the functional checks required at hot and cold conditions. For batch specimens, define spacing and monitoring positions so one sample or rack does not unintentionally shield another from the circulating air.
A typical profile contains a starting condition, a controlled transition, a dwell, a return transition and a repeat count. The chamber recipe should reproduce this sequence while preserving a record of actual conditions and any interruption.
This is a temperature-humidity chamber, not a temperature-only room. Include humidity stages when your method requires them, with the simultaneous temperature–RH operating points identified in the selected configuration.

02 · Technical parameters
DERUI 10 m³ thermal chamber
10m³ Technical Parameters and Configuration Choices
Select the temperature and humidity configuration for your actual test. The range selections below describe alternatives; the ordered chamber must have one defined configuration and a measurable performance specification.
| Parameter | Configuration | Application condition |
|---|---|---|
| Nominal workspace | 10m³ | Internal dimensions, usable zone, door opening and floor capacity are specified with the loading drawing. |
| High-temperature limit selections | +80 / +100 / +120 / +150 / +200°C | Alternative configurations, not simultaneous ratings for one installed machine. Select the required upper limit in the proposal. |
| Low-temperature limit selections | 0 / −20 / −40 / −50 / −60 / −70°C | Alternative configurations. Confirm the chosen low/high combination with the required load and installation conditions. |
| Humidity range selections | 30–98 / 25–95 / 20–98 / 10–98% RH | Select the installed humidity configuration and its temperature–RH envelope. These are not interchangeable universal ratings. |
| temperature deviation | ≤ ±1°C | Agree the measurement definition, setpoints, sensor positions and load conditions. This value is not a substitute for a separate uniformity requirement. |
| temperature fluctuation | ≤ ±0.5°C | Define the stabilization and observation period used for verification. |
| humidity error | +2 / −3% RH | Confirm applicable temperature–RH points and measurement conditions. |
| average heating rate | 1–3°C/min | Average-rate reference; interval and loading conditions must be specified. Not a guaranteed linear or specimen rate. |
| average cooling rate | 1°C/min | Average-rate reference; verify the selected interval, load and powered heat output. |
| Cooling arrangement | Water-cooled | Obtain required water temperature, flow, pressure, quality and heat-rejection duty for the selected system. |
| Control and program capacity | PID program control; 120 programs / 1,200 segments | Allocate stages and cycles around the test recipe; confirm the controller implementation in the ordered configuration. |
| Construction material | SUS304 stainless steel | Specify the required surface, floor construction and load capacity in the mechanical configuration. |
| Electrical arrangement | Three-phase, four-wire | Destination voltage, frequency, rated power and protective-device requirements are project-specific. |
| Operating functions | Programmed temperature and humidity | Controller functions and interfaces are detailed below; agree the supplied configuration before purchase. |
03 · Thermal cycling
DERUI 10 m³ thermal chamber
Average Air Rate Is Not a Guaranteed Specimen Rate
For a programmed temperature cycle, define what is being controlled and measured. Chamber air can reach the target before a heavy component stabilizes. A temperature displayed at the control sensor does not establish that every sample has completed its required exposure.
| Requirement | Define in the test plan | Why it matters |
|---|---|---|
| Ramp or transition | Start/end temperatures, average or linear rate, and air or specimen measurement | An average rate over one interval does not establish the slope across every part of a cycle. |
| Dwell | Start condition, tolerance and duration | Starting the dwell too early can shorten the specimen’s intended exposure. |
| Loading | Specimen and fixture mass, layout, material and internal heat output | Thermal mass affects response; powered heat affects cooling duty and local temperatures. |
| Humidity stages | Paired temperature–RH points and condensation requirements | Separate range limits do not establish every simultaneous operating condition. |
| Functional monitoring | Operating state, cable interfaces, measurement points and termination rules | A repeatable exposure needs repeatable specimen operation and result assessment. |
When discussing temperature-change testing under IEC 60068-2-14, identify the adopted edition and exact procedure. Match its transition, exposure and specimen requirements to a demonstrated chamber capability. A standard name in a quotation does not establish suitability for every test severity.
Thermal cycling is not rapid-transfer thermal shock. This page describes programmed heating and cooling in a walk-in room. Do not substitute it for a hot-to-cold transfer system, or assume fast-rate ESS performance from the average rates.
Before acceptance, run the specified cycle with a representative load or an agreed substitute. Record chamber air and any required specimen temperatures, then evaluate the rate and dwell using the same definitions as the purchase specification.
04 · Control and records
DERUI 10 m³ thermal chamber
Build a Traceable Recipe, Not Just a Completed Cycle
Recipe and access control
The controller functions include Chinese/English touchscreen menus, password-based access, scheduled operation and program status displays. Set permissions so routine operation does not change an approved recipe unnoticed.
Curve recording and export
The functions include paperless curves, timestamped records, XLS table export and USB data export. Specify which channels, sampling interval, file format and identifiers must appear in your test record.
Network and interruption handling
Ethernet/TCP/IP monitoring and selectable power-failure recovery are described in the listing. Align network access with your IT rules; choose restart, resume or stop behavior appropriate to the test, rather than resuming every cycle automatically.
Retain the specimen ID, approved recipe, actual temperature-humidity records, operating state, alarm history and post-test assessment together. A chamber record shows environmental exposure; functional inspection or product acceptance remains a separate evaluation.
If you need specimen thermocouples or other independent acquisition channels, define them separately from the controller’s air-temperature record. Test the actual export process during handover, including timestamps and how an operator associates a file with the correct specimen.
The listed protections include compressor pressure/current/temperature protection, fan overheating protection, temperature limits and electrical protection. Define alarm thresholds, specimen power isolation and the required response to a fault in the ordered system. Battery or hazardous-material testing requires an additional risk review; these protections are not evidence of explosion containment.
05 · Installation and acceptance
DERUI 10 m³ thermal chamber
Prepare the Water Circuit, Loading Layout and Acceptance Cycle
A water-cooled installation needs more than a suitable electrical connection. Establish the water supply and heat-rejection arrangement before delivery. Request an installation drawing identifying service connections, environmental-system access and the loading space around the chamber.
| Project decision | Information to provide / request | Acceptance check |
|---|---|---|
| Cooling-water services | Available inlet temperature, flow, pressure, water quality and return arrangement | Verify the selected system’s required services and record conditions during the acceptance run. |
| Mechanical loading | Product, rack and trolley dimensions; distributed and point loads | Review clear access, floor capacity and supply/return-air clearance. |
| Electrical and interfaces | Site voltage/frequency, operating specimen power, signal and fluid connections | Verify supply compatibility, protective functions and the ordered test-port arrangement. |
| Environmental performance | Selected range, rate interval, tolerances, paired RH points and representative load | Measure performance against the agreed recipe and measurement definitions. |
| Controls and handover | Recipes, export needs, alarm responses and maintenance access | Demonstrate control functions, data export and safe recovery from the agreed fault scenarios. |
Separate factory acceptance testing from checks dependent on the installed site and actual specimen. IEC 60068-3-7 provides guidance for loaded temperature-chamber measurements in cold and dry-heat testing. Use applicable guidance in the acceptance plan without turning it into a claim of product certification.
Compare proposals using the same selected range, test load, heat output, rate definition, water conditions and acceptance scope. If energy use is important, request measured consumption under a defined duty; compare equivalent cycles instead of relying on an unsupported percentage saving.
06 · Buyer questions
DERUI 10 m³ thermal chamber
Compare the complete supply scope
Develop room geometry, door opening, floor structure, conditioning plant and specimen services together. Include unloading, site access, assembly space, electrical connection, cooling services, drainage and heat rejection in the installation plan. Nominal volume does not define usable rack capacity or door clearance.
DERUI 10 m³ thermal chamber
Choose the configuration for your application
Heating, cooling and dwell for large or rack-mounted assemblies.
Configure door geometry, reinforced floor, ramps, racks, feedthroughs, cooling method and independent measurement channels around the specimen and site. Where humidity is required, specify paired temperature–RH points rather than assuming the full temperature and humidity maxima can occur simultaneously.
DERUI 10 m³ thermal chamber
Agree the factory acceptance record
Use the approved loading drawing to check door travel, trolley access, floor loads and airflow paths. Verify temperature and humidity at the agreed points and operating conditions with the relevant specimen heat load. Record safety release, alarm operation, programme execution and data exports. Empty-room mapping and loaded process performance should be distinguished in the acceptance record.
DERUI 10 m³ thermal chamber
Compare related equipment
Prepare the 10m³ Walk-In Temperature Chamber enquiry
Send the following information together so the proposed equipment, accessories and acceptance scope match your test:
- Specimen rack and trolley
- low/high temperature and transitions
- specimen mass and powered heat
- optional RH points
- site and door/floor requirements
List the required fixtures, measurement channels, data records and installation services separately in the quotation. Agree the representative specimen arrangement and pass criteria before the equipment acceptance run.
Request a 10 m³ thermal chamber proposal
Send these details so the quotation covers your actual application:
- Specimen rack and trolley
- Low/high temperature and transitions
- Specimen mass and powered heat
- Optional rh points
- Site and door/floor requirements















